Implementing financially viable efficiency measures and optimising gas heating became mandatory for all building owners with natural gas heating.
Building owners with gas heating are affected
The regulation that took effect in October 2022 requires all owners of buildings using natural gas to generate heatto have a heating inspection carried out and the building’s heating system optimised. This applies regardless of building size, so operators of individual gas heating systems in apartments are also required to have them checked.
The Regulation to Secure Energy Supply through Measures Effective in the Medium Term has applied since 1 October 2022. It provides three basic elements for inspecting, assessing and optimising gas heating systems.
1. Heating inspection
The company The heating inspection must be carried out by a qualified person. This includes specialist tradespeople and heating installers, as well as chimney sweeps and energy consultants. It is sensible to combine the inspection with the next maintenance visit to avoid separate travel costs.
The inspection assesses:
Whether the heating system can operate with optimised technical parameters
Whether hydraulic balancing is necessary
Whether high-efficiency pumps are already installed
Whether pipe insulation has been installed in accordance with regulations
The heating inspection identifies optimisation measures. These primarily concern system settings, such as savings through lower flow temperatures or an optimised heating curve. Changes to night setback or heating cut-off temperatures are also included.
2. Hydraulic balancing
In addition to mandatory heating inspections, the regulation introduces mandatory hydraulic balancing for the first time. Balancing must be completed by 30 September 2023, an immense challenge given the current shortage of skilled workers.
Balancing is required for:
Residential buildings with at least 10 units
Non-residential buildings with more than 1,000 m² of heated floor area
And, by 15 September 2024, buildings with 6 or more residential units
Hydraulic balancing must include the following design services:
Room-by-room heat load calculation to DIN EN 12831:2017-09
Checking and, where necessary, optimising heat emitters for the lowest possible flow temperature
Hydraulic balancing taking account of all essential heating system components, and
Adjustment of flow temperature controls
In many cases, this will require more design work. Where complete building documentation is unavailable, the design company must calculate room-by-room heat loads using all available information, floor plans and building envelope details. If design documentation for riser and pump sizing is missing, these must also be recalculated before hydraulic balancing can take place. The presence or installation of presettable radiator valves is a basic requirement.
Kraftland GmbH offers comprehensive support with all these obligations. With suitable software, hardware and trained staff, we have prepared for EnSimiMaV requirements and look forward to hearing from you.